This is a listing of all current truck, trailer, CR, DAS and DSR alarm codes. On multi-temp units, the zone will be identified. Please record all alarms that occur to assist technician in resolving issue. Alarm codes with parenthesis (XX) may exist with alarm code 84 and may clear automatically.
Description: No Alarms Exist
Operator Action: No action required.
Description: Check Evaporator Coil Sensor (Zone)
Operator Action: Manually monitor temperature. Report alarm at end of day.
Description: Check (Control) Return Air Sensor (Zone)
Operator Action: Manually monitor temperature. Report alarm at end of day.
Description: Check (Control) Discharge Air Sensor (Zone)
Operator Action: Manually monitor temperature. Report alarm at end of day.
Description: Check Ambient Temp Sensor
Operator Action: Report alarm at end of day.
Description: Check Coolant Temp Sensor
Operator Action: Report alarm at end of day.
Description: Check Engine RPM Sensor
Operator Action: Report alarm at end of day.
Description: Unit Running on Coil Sensor (Zone)
Operator Action: Manually monitor temperature. Report alarm at end of day.
Description: High Evaporator Temperature (Zone)
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
Description: High Discharge Pressure (or Temperature)
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Unit or Zone Controlling on Alternate Sensor (Zone)
Operator Action: Manually monitor temperature. Report alarm at end of day.
Description: Sensor or Digital Input Shutdown (Zone)
Operator Action: Unit/zone cannot operate and is shut down. Repair immediately.
Description: Sensor Check (Zone)
Operator Action: Manually monitor temperature. Report alarm at end of day.
Description: Defrost Terminated by Time
Operator Action: Report alarm at end of day.
Description: Check Glow Plugs or Intake Air Heater
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Manual Start Not Completed
Operator Action: Report alarm at end of day.
Description: Engine Failed to Crank
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: High Engine Coolant Temperature
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Low Engine Oil Pressure
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Engine (Vapor Motor CR) Failed to Start
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Cooling Cycle Check (Zone)
Operator Action: Manually monitor temperature. Report alarm at end of day.
Description: Heating Cycle Check (Zone)
Operator Action: Manually monitor temperature. Report alarm at end of day.
Description: Cooling Cycle Fault (Zone)
Operator Action: Unit/zone cannot operate and is shut down. Repair immediately.
Description: Heating Cycle Fault (Zone)
Operator Action: Unit/zone cannot operate and is shut down. Repair immediately.
Description: Alternator Check
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Check Refrigeration Capacity (Zone)
Operator Action: Manually monitor temperature. Report alarm at end of day.
Description: Vapor Motor RPM High (CR)
Operator Action: Unit cannot operate and is shut down. Repair immediately.
Description: Pretrip or Self Check Abort
Operator Action: Report alarm at end of day.
Description: Defrost Damper Circuit Check (Zone)
Operator Action: Manually monitor temperature. Report alarm at end of day.
Description: Defrost Damper Stuck Closed (Zone)
Operator Action: Unit/zone cannot operate and is shut down. Repair immediately.
Description: Check Oil Pressure Switch
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Refrigeration Capacity Low (Zone)
Operator Action: Unit/zone cannot operate and is shut down. Repair immediately.
Description: Check Engine RPM
Operator Action: Report alarm at end of day.
Description: Check Modulation Circuit
Operator Action: Manually monitor temperature. Report alarm at end of day.
Description: Check Run Relay Circuit
Operator Action: Unit cannot operate and is shut down. Repair immediately.
Description: Electric Motor Failed to Run
Operator Action: Unit cannot operate and is shut down. Repair immediately. Switch to Diesel Mode
Description: Check Engine Coolant Level
Operator Action: Report alarm at end of day.
Description: Electric Phase Reversed
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Check Water Valve Circuit
Operator Action: Manually monitor temperature. Report alarm at end of day.
Description: Check High Speed Circuit
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Check Engine Coolant Temp
Operator Action: Report alarm at end of day.
Description: Unit Forced to Low Speed
Operator Action: Report alarm at end of day.
Description: Unit Forced to Low Speed Modulation
Operator Action: Report alarm at end of day.
Description: Check Fuel System
Operator Action: Add fuel as necessary. Otherwise, report alarm at end of day.
Description: Check Hot Gas or Hot Gas Bypass Circuit
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Check Air Flow (Zone)
Operator Action: Manually monitor temperature. Report alarm at end of day.
Description: Remote Sensor Shutdown
Operator Action: Unit/zone cannot operate and is shut down. Repair immediately.
Description: Check Belts or Clutch
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Check Spare Sensor 1
Operator Action: Report alarm at end of day.
Description: Reset Clock
Operator Action: Report alarm at end of day.
Description: Check Shutdown Circuit
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Check Heat Circuit (Zone)
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Check Economizer Valve Circuit
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Test Mode Timeout
Operator Action: Clear alarm and restart unit.
Description: Check Engine Speeds
Operator Action: Report alarm at end of day.
Description: Check Evaporator Fan Low Speed (Zone)
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Check Evaporator Fan High Speed (Zone)
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Low Battery Voltage
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Ammeter Out of Calibration
Operator Action: Unit cannot operate and is shut down. Repair immediately.
Description: Engine or Vapor Motor Stopped
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Pretrip Reminder
Operator Action: Report alarm at end of day.
Description: Abnormal Temperature Differential (Zone)
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Low Engine Oil Level
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Check Liquid Line Solenoid Circuit (Zone)
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Internal Controller Fault Code
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Hourmeter Failure
Operator Action: Report alarm at end of day.
Description: Hourmeter 4 Exceeds Set Time Limit
Operator Action: Report alarm at end of day.
Description: Hourmeter 5 Exceeds Set Time Limit
Operator Action: Report alarm at end of day.
Description: Hourmeter 6 Exceeds Set Time Limit
Operator Action: Report alarm at end of day.
Description: Controller Reset to Defaults
Operator Action: Report alarm at end of day.
Description: Controller RAM Failure
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Controller EPROM Failure
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Controller EPROM Checksum Failure
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Data Log EPROM Failure
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Internal Data Logger Overflow
Operator Action: Report alarm at end of day.
Description: Check Compressor Temp Sensor
Operator Action: Report alarm at end of day.
Description: High Compressor Temp
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: High Compressor Temp Shutdown
Operator Action: Unit cannot operate and is shut down. Repair immediately.
Description: Low Engine Coolant Temp
Operator Action: Report alarm at end of day.
Description: Restart Null
Operator Action: Report alarm at end of day.
Description: Forced Unit Operation
Operator Action: Report alarm at end of day.
Description: Check Discharge Pressure Sensor
Operator Action: Report alarm at end of day.
Description: Check Suction Pressure Sensor
Operator Action: Report alarm at end of day.
Description: Reserved for CR
Description: Check Electronic Throttling Valve (ETV) Circuit
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Electric Overload
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Check Electric Ready Input
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Sensor Grades Not Set (Zone)
Operator Action: Report alarm at end of day.
Description: Low Compressor Suction Pressure
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Check Loader #1 Circuit
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Check Loader #2 Circuit
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Low Fuel Level
Operator Action: Add fuel as required.
Description: Failed Remote Return Air Sensor (CR)
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Check Fuel Level Sensor
Operator Action: Report alarm at end of day.
Description: High Compressor Pressure Ratio
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Heater Fan Failure (CR)
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Controlling on Evap Coil Outlet Temp (CR)
Operator Action: Manually monitor temperature. Report alarm at end of day.
Description: Low Evaporator Coil Temperature (CR)
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Low Heater Fuel Level (CR)
Operator Action: Manually monitor temperature. Report alarm at end of day.
Description: Check Remote Fan Speed (Zone)
Operator Action: Manually monitor temperature. Report alarm at end of day.
Description: Check Receiver Tank Press Sol Circuit
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Check Purge Valve Circuit
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Check Condenser Inlet Sol Circuit
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Door Open Timeout (Zone)
Operator Action: Close doors. Report alarm at end of day.
Description: Check High Discharge Pressure Sensor
Operator Action: Replaced by Alarm Code 86
Description: Check Suction Line Sol Circuit (Zone)
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Unit Not Configured Correctly (Zone)
Operator Action: Report alarm at end of day.
Description: Check Remote Fans (Zone)
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Check Electric Heat Circuit (Zone)
Operator Action: Manually monitor temperature. Report alarm at end of day.
Description: Multiple Alarms - Can Not Run (Zone)
Operator Action: Unit/zone cannot operate and is shut down. Repair immediately.
Description: Check High Pressure Cut Out Switch
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Check High Pressure Cut In Switch
Operator Action: Report alarm at end of day.
Description: Auto Switch from Diesel to Electric
Operator Action: Normal operation – does not affect performance.
Description: Auto Switch from Electric to Diesel
Operator Action: Normal operation – does not affect performance.
Description: Reserved for CR
Description: Check Alternator Excite Circuit
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Check PMW Liquid Injection Circuit
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Check Diesel/Electric Circuit
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Check Evap Coil Inlet Temp Sensor (CR)
Operator Action: Manually monitor temperature. Report alarm at end of day.
Description: Check Evap Coil Outlet Temp Sensor (CR)
Operator Action: Report alarm at end of day.
Description: Check Tank Level Sensor (CR)
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Check Back Pressure Regulator (CR)
Operator Action: Manually monitor temperature. Report alarm at end of day.
Description: Setpoint Not Entered (Zone)
Operator Action: Be sure setpoint is adjusted to required temperature.
Description: Engine Run Time Maint Reminder #1/Service Due
Operator Action: Report alarm at end of day.
Description: Engine Run Time Maint Reminder #2
Operator Action: Report alarm at end of day.
Description: Engine Run Time Maint Reminder #1
Operator Action: Report alarm at end of day.
Description: Electric Run Time Maint Reminder #2
Operator Action: Report alarm at end of day.
Description: Total Unit Run Time Maint Reminder #1
Operator Action: Report alarm at end of day.
Description: Total Unit Run Time Maint Reminder #2
Operator Action: Report alarm at end of day.
Description: Controller Power On Hours
Operator Action: Report alarm at end of day.
Description: Check Spare Digital Inputs
Operator Action: Report alarm at end of day.
Description: Check Spare Digital Outputs
Operator Action: Report alarm at end of day.
Description: Check Damper Motor Heater Output
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Log DAS Real Time Clock Battery Failure (DAS)
Operator Action: Report alarm at end of day.
Description: Abort Evacuation Mode
Operator Action: Report alarm at end of day.
Description: Not currently used
Description: Auto Switch Diesel to Electric Disabled
Operator Action: Report alarm at end of day.
Description: Check Thermax Valve
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Check Remote Drain Hose Heater Output (Zone)
Operator Action: Report alarm at end of day.
Description: Lost CAN Communications to Expansion Module
Operator Action: Unit cannot operate and is shut down. Repair immediately.
Description: Lost Controller ON Feedback Signal
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Software Version Mismatch
Operator Action: Report alarm at end of day.
Description: Check Multi-Temp Fan Speed Control Output (Zone)
Operator Action: Manually monitor temperature. Report alarm at end of day.
Description: Auto Switch Electric to Diesel Disabled
Operator Action: Report alarm at end of day.
Description: Alarm Not Identified
Operator Action: If unit/zone is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Sensor Out of Range Low (DAS and HMI) (Zone)
Operator Action: Report alarm at end of day.
Description: Sensor Out of Range High (DAS and HMI) (Zone)
Operator Action: Report alarm at end of day.
Description: DAS Failed Sensor (DAS)
Operator Action: Report alarm at end of day.
Description: Expansion Module Flash Load Failure
Operator Action: Report alarm at end of day.
Description: Low Suction Pressure Switch Failure
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Lost CAN Communications to HMI
Operator Action: Unit cannot operate and is shut down. Repair immediately.
Description: Check Suction/Liquid Heat Exchanger Bypass Valve
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: OptiSet Plus Profile Mismatch
Operator Action: Report alarm at end of day.
Description: Primary Software Failed to Load
Operator Action: Report alarm at end of day.
Description: Check Battery Condition
Operator Action: Report alarm at end of day.
Description: Lost CAN Communications to Radio Expansion Board
Operator Action: Report alarm at end of day.
Description: Log DAS Real Time Clock Invalid (DAS)
Operator Action: Report alarm at end of day.
Description: Emission Control Failure
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Check Electronic Expansion Valve (CR)
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Check Evaporator Pressure Sensor (CR)
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Check CO2 Tank Pressure Sensor (CR)
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Low CO2 Fuel Level (CR)
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: TriPac Compressor Alarm
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Log DAS Microprocessor Fault (DAS)
Operator Action: Report alarm at end of day.
Description: Check Display Return Air Sensor (Zone)
Operator Action: Manually monitor temperature. Report alarm at end of day.
Description: Check Display Discharge Air Sensor (Zone)
Operator Action: Manually monitor temperature. Report alarm at end of day.
Description: Check DAS Digital Inputs (DAS)
Operator Action: Report alarm at end of day.
Description: REB Switching Off, Conservative to Full Null
Operator Action: Report alarm at end of day.
Description: Check Relative Humidity Sensor Circuit
Operator Action: Report alarm at end of day.
Description: High Engine Coolant Temperature Check
Operator Action: Report alarm at end of day.
Description: DAS Clock Time Reset (DAS)
Operator Action: Report alarm at end of day.
Description: Check Radio Expansion Board Configuration
Operator Action: Report alarm at end of day.
Description: Check Auto Fresh Air Exchange Circuit
Operator Action: Report alarm at end of day.
Description: REB On Back Up Battery, Alarms Disabled
Operator Action: Report alarm at end of day.
Description: Check Auxiliary Coolant Temp Sensor
Operator Action: Report alarm at end of day.
Description: Check Host Evaporator Blower Low Speed
Operator Action: Not implemented
Description: Check Host Evaporator Blower High Speed
Operator Action: Not implemented
Description: Check Roadside Condenser Fan Motor Speed Circuit
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Check Curbside Condenser Fan Motor Speed Circuit
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Check Digital Scroll Output Circuit (Scroll Only)
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Speed Request Communication Error
Operator Action: Report alarm at end of day.
Description: ECU Failed to Enable
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: ECU Run Signal Failed
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Engine Wait to Start Time Delay Expired
Operator Action: Report alarm at end of day.
Description: High Compressor Suction Pressure (Scroll Only)
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Low Compressor Suction Ratio (Scroll Only)
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Low Compressor Discharge Pressure (Scroll Only)
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Minimum ETV Discharge Superheat Temp (Scroll)
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: I/O Controller to Application Controller Com Failure
Operator Action: The unit is no longer able to operate and has been shut down. Repair immediately.
Description: Generator Ground Fault
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Check Battery Charger Input Power
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Check Battery Charger Output Power
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Battery Charger External/Environmental Fault
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Battery Temperature Sensor Alarm
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Battery Charger Indicated Conditions
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Generator Op Limit Vout to Frequency Ration
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Generator Frequency Range Fault
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Generator Operational Limit Output Current
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Failed J1939 CAN Comm Base Controller/Charger
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Check Fuel Pump Circuit
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Low Pressure Differential (Scroll only)
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Check Economizer Pressure Sensor (Scroll only)
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Engine J1939 CAN Data Link Degraded
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Engine J1939 CAN Data Link Failed
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Illegal Engine Operating State
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Battery Charger Fault – Unit Forced to Low Speed
Operator Action: Maintenance information only. Report alarm at end of day.
Description: Battery Charger Internal Short
Operator Action: Maintenance information only. Report alarm at end of day.
Description: Battery Charger External Short
Operator Action: Maintenance information only. Report alarm at end of day.
Description: Battery Charger Output Voltage Exceeded Limit
Operator Action: Maintenance information only. Report alarm at end of day.
Description: Battery Charger Operating Bulk Voltage Out of Range
Operator Action: Maintenance information only. Report alarm at end of day.
Description: AC Bus Phase Loss
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Battery Charger Temperature Below Operating Range
Operator Action: Maintenance information only. Report alarm at end of day.
Description: Battery Charger AC Input Overvoltage
Operator Action: Maintenance information only. Report alarm at end of day.
Description: Battery Charger Internal Overvoltage Fault
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Battery Charger Internal Temp Sensor Fault
Description: Battery Charger Charging – Low Battery
Description: Battery Charger Operating Derated Due to High temp
Description: Engine Service Tool Connected
Operator Action: Report alarm at end of day.
Description: Check Crankshaft Speed Sensor
Operator Action: Report alarm at end of day.
Description: Check Camshaft Speed Sensor
Operator Action: Report alarm at end of day.
Description: Check Exhaust Pressure Sensor
Operator Action: Report alarm at end of day.
Description: Check Coolant Temp Sensor
Operator Action: Report alarm at end of day.
Description: Check Fresh Air Temp Sensor
Operator Action: Report alarm at end of day.
Description: Check Fuel Temperature Sensor
Operator Action: Report alarm at end of day.
Description: Check Rail Pressure Sensor
Operator Action: Report alarm at end of day.
Description: Check Intake Pressure Sensor
Operator Action: Report alarm at end of day.
Description: Check Atmospheric Pressure Sensor
Operator Action: Report alarm at end of day.
Description: Check Glow Plug Circuit
Operator Action: Report alarm at end of day.
Description: Check Injectors
Operator Action: Report alarm at end of day.
Description: Check High Pressure Fuel Pump
Operator Action: Report alarm at end of day.
Description: Rail Pressure Fault
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Engine Overspeed
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Internal ECU Fault
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Check EGR System
Operator Action: Report alarm at end of day.
Description: ECU Main Relay Fault
Operator Action: Report alarm at end of day.
Description: No RPM Detected During Start Attempt
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: TRUCAN Message Timeout
Operator Action: Report alarm at end of day.
Description: Check EGR Temperature Sensor
Operator Action: Report alarm at end of day.
Description: Check Intake Air Temperature Sensor
Operator Action: Report alarm at end of day.
Description: Check Exhaust Temperature Sensor
Operator Action: Report alarm at end of day.
Description: ECU Forced Low Speed
Operator Action: Report alarm at end of day.
Description: Unknown ECU Fault
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Crankshaft Position Sensor Error
Operator Action: Report alarm at end of day.
Description: Camshaft Position Sensor Error
Operator Action: Report alarm at end of day.
Description: Engine Coolant Temperature Sensor Error
Operator Action: Report alarm at end of day.
Description: Fuel Temperature Sensor Error
Operator Action: Report alarm at end of day.
Description: Rail Pressure Sensor Error
Operator Action: Report alarm at end of day.
Description: Intake Air Pressure Sensor Error
Operator Action: Report alarm at end of day.
Description: Atmospheric Pressure Sensor Error
Operator Action: Report alarm at end of day.
Description: Glow Plug Circuit Error
Operator Action: Report alarm at end of day.
Description: General Injector Error
Operator Action: Report alarm at end of day.
Description: Fuel Pressure Regulator Error
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: EGR Valve Actuator Error
Operator Action: Report alarm at end of day.
Description: ECU Power Relay Error
Operator Action: Report alarm at end of day.
Description: Main ECU Relay Error
Operator Action: Report alarm at end of day.
Description: T1 Air Intake Temperature Sensor Error
Operator Action: Report alarm at end of day.
Description: T2 Air Intake Temperature Sensor Error
Operator Action: Report alarm at end of day.
Description: EGR Valve Position Sensor Error
Operator Action: Report alarm at end of day.
Description: Lambda System Error
Operator Action: Report alarm at end of day.
Description: Engine Communication Error
Operator Action: Report alarm at end of day.
Description: Air Flow Meter Error
Operator Action: Report alarm at end of day.
Description: Engine Power Supply Error
Operator Action: Report alarm at end of day.
Description: High Pressure Pump Fuel Metering Unit Error
Operator Action: Report alarm at end of day.
Description: Water in Fuel Sensor Error
Operator Action: Report alarm at end of day.
Description: Major ECU Failures
Operator Action: Report alarm at end of day.
Description: Intake Air System Error
Operator Action: Report alarm at end of day.
Description: Engine Speed Error
Operator Action: Report alarm at end of day.
Description: Fuel Injection Energizing Error
Operator Action: Report alarm at end of day.
Description: High Pressure Pump Wear
Operator Action: Report alarm at end of day.
Description: Engine Running in Safe Mode – Low Speed
Operator Action: Report alarm at end of day.
Description: Fuel Injection System Error
Operator Action: Report alarm at end of day.
Description: Engine Failed to Crank
Operator Action: Report alarm at end of day.
Description: Starter Relay Error
Operator Action: Report alarm at end of day.
Description: T50 Switch Error
Operator Action: Report alarm at end of day.
Description: Variant Coding Error
Operator Action: Report alarm at end of day.
Description: Engine Overspeed (No DTC)
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Engine Protection Self Shutdown
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Unknown ECU Fault
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Return Air Temperature Sensor Fault
Operator Action: Report alarm at end of day.
Description: Remote Return Air Temperature Sensor Fault
Operator Action: Report alarm at end of day.
Description: Electric Standby Overload
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Low Battery Voltage
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: High Discharge Pressure
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Low Suction Pressure
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: High Pressure Sensor Fault
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Electric Standby Motor Thermal Protection Alarm
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Power Supply Thermal Protection Alarm
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Door 1 Open/Door Switch 1 Failure
Operator Action: Close door. Report alarm at end of day.
Description: Door 2 Open/Door Switch 2 Failure
Operator Action: Close door. Report alarm at end of day.
Description: Electronic Control Module Internal Temperature Exceeds Limit
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Microprocessor Software Failure
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.
Description: Communications Failure, Microprocessor to In-Cab Control Box
Operator Action: If unit is shut down repair immediately. Otherwise, report alarm at end of day.